WhatsApp/WeChat/Skype/Phone:+8618625503172
477 MCM PELICAN ACSR Conductor Cable
ASTM B232
Aluminium has become widely adopted as an electrical conductor material, largely due to its favorable electrical properties. However, for most long-span transmission lines, aluminium conductors require additional mechanical support—galvanized steel wires are commonly used as the core in ACSR conductors to address this need.
| Construction characteristics | |
| Type of cable | Pelican |
| Type of conductor | Circular, stranded |
| Conductor material | aluminum / Steel Core |
| Conductor flexibility | Class AA |
| Conductor shape | Circular non compacted |
| Dimensional characteristics | |
| Conductor cross-section | 477 kcmil |
| Aluminium cross-section | 242.31 mm² |
| Conductor cross-section | 255.77 mm² |
| Number of aluminium wires | 18 |
| Diameter of aluminium wires | 4.14 mm |
| Number of steel wires | 1 |
| Diameter of steel wires | 4.14 mm |
| Diameter of steel core | 4.14 mm |
| Conductor diameter | 20.7 mm |
| Average geometric radius | 0.00803 m |
| Aluminium content | 668.1 kg/km |
| Steel content | 104.7 kg/km |
| Approximate weight | 772.8 kg/km |
| Nominal outer diameter | 20.7 mm |
| Number of cores | 1 |
| Number of round wires | 19 |
| Electrical characteristics | |
| Max. DC resistance of the conductor at 20°C | 0.119 Ohm/km |
| Max. electric resistance AC 60Hz 75°C | 0.145 Ohm/km |
| Inductive reactance | 0.3639 Ohm/km |
| Capacitive reactance | 0.2182 MOhm.km |
| Ampacity | 640.0 A |
| Mechanical characteristics | |
| Rated breaking load (Class A) | 5445 kgf |
| Rated breaking load (Class B) | 5363 kgf |
| Hardness type | 1350-H19 |